The product is in accordance with standards of VDE 0664,CEE27 and BS4293 etc.
◆Application
The product is in accordance with standards of VDE 0664,CEE27 and BS4293 etc.Applying to the circuit of AC 50/60Hz, 240V single phase, 415V three phases and below it for industrial and mining enterprise, shopping mall, commerce and family. To mainly prevent electric fire and personal casualty accident caused by personal electric shock or leakage of electrified wire netting, this ELCB is a current-operated,fast leakage protector of pure electromagnetic type.VVhich can break off fault circuit rapidly in order to avoid occurrence of accident. The item is precise in structure, less elements,without auxiliary power and high working reliability.The function of the switch will not be influenced by ambient temperature and lighting. The mutual inductor of the item is used to test vector differential value of passing current,and produces are relevant output power and add it differential value of protected circuit of personal electric shock is up to or over leakage operating current, the tripper will act and cut off so that the item will take effect of protection.
◆Specifications
Tripping Time | 100ms(depending on specifications 5XIL,400ms) |
Ambient Temperature | -5℃ ~+55℃ |
Climatic Resistance | 55℃ / 28℃ cycles |
Vibration Resistance | Min 5g 30min, 0-8Hz |
Life Expectance | More Than 10,000 Times |
◆Wiring Diagram
Type | RatedCurrent (A) | Leakage Acting Current | Range of Break-off | Rated Voltage |
CEB6L 2P | 16A,25A,32A ,40A,63A | 10mA 30mA 100mA 300mA | 0.5~1.0XI△n | 240V(220V) |
CEB6L 4P | 25A,32A | 30m 100mA 300mA | 0.5~1.0XI△n | 240V/415V (220V/380V) |
◆Operation Principle Fig.
◆Dimensions