CMB2-ME series motor protection circuit breaker are mainly used for the overload and short circuit protection of the motor in AC 50/60Hz,up to 660V,0.1-80A,as a full-voltage starter to start and stop the motor,under theAC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.
◆Application
CMB2-ME series motor protection circuit breaker are mainly used for the overload and short circuit protection of the motor in AC 50/60Hz,up to 660V,0.1-80A,as a full-voltage starter to start and stop the motor,under theAC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.
◆Specifications
Type | Standard Power Ratings of 3-phase Motors 50/60Hz in Category AC-3 | Setting | |||||
220V KW | 380V KW | 415V KW | 440V KW | 500V KW | 660V KW | ||
CMB2-ME01/RS01 | - | - | - | - | - | - | 0.1-0.16 |
CMB2-ME02/RS02 | - | - | - | - | - | - | 0.16-0.25 |
CMB2-ME03/RS03 | - | - | - | - | - | - | 0.25-0.4 |
CMB2-ME04/RS04 | - | - | - | - | - | 0.37 | 0.4-0.63 |
CMB2-ME05/RS05 | - | - | - | 0.37 | 0.37 | 0.55 | 0.63-1 |
CMB2-ME06/RS06 | - | 0.37 | - | 0.55 | 0.75 | 1.1 | 1-1.6 |
CMB2-ME07/RS07 | 0.37 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.6-2.5 |
CMB2-ME08/RS08 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 3 | 2.5-4 |
CMB2-ME10/RS10 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 | 4-6.3 |
CMB2-ME14/RS14 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 | 6-10 |
CMB2-ME16/RS16 | 3 | 5.5 | 5.5 | 7.5 | 7.5 | 9 | 9-14 |
CMB2-ME20/RS20 | 4 | 7.5 | 9 | 9 | 9 | 11 | 13-18 |
CMB2-ME21/RS21 | 5.5 | 11 | 11 | 11 | 11 | 15 | 17-23 |
CMB2-ME22/RS22 | 5.5 | 11 | 11 | 11 | 15 | 18.5 | 20-25 |
CMB2-ME32/RS32 | 7.5 | 15 | 15 | 15 | 18.5 | 26 | 24-32 |