FW26 series changeover switch is used in the circuits of AC 50Hz,rated voltage up to 690V,DC voltage up to 240V,rated current up to 100A...
◆Specifications
FW26 series changeover switch is used in the circuits of AC 50Hz,rated voltage up to 690V,DC voltage up to 240V,rated current up to 100A,to not frequently switch on/off circuit,transfer and control circuits,also it can directly control small capacity motor or be used for master control or electric meters.The switch is used widely in circuit control,test equipment,switch for motor, master control,welding machine and etc.
Advantages:small size,multifunction,compact structure,high quality material,good in sulation,agile operation,reliability,safety,good appearance.FW26-20,FW26-25,FW26-32,FW26-63,provide function of finger protection.
◆Specifications
Model | FW26-10 | FW26-20 | FW26-25 | ||||||
Rated Insulation Voltage Ui (V) | 690V | ||||||||
Rated Thermal Current Lth (A) | 10 | 20 | 25 | ||||||
Rated Operating Voltage Ue (V) | 220 | 380 | 500 | 220 | 380 | 500 | 220 | 380 | 500 |
AC-21A AC-22A(A) | 10 | 20 | 20 | ||||||
AC-2 3P(KW) | 2 | 3.5 | 7 | 4 | 7.5 | 10 | 5.5 | 11 | 13 |
AC3 3P/1P(KW)) | 1/0.5 | 3.5/1 | 2.5 | 3/2.2 | 5.5/3 | 5.5 | 4/3 | 7.5/3.7 | 7.5 |
AC-4 3P/1P(KW) | 0.25/0.35 | 1/1.5 | 1 | 0.55/0.75 | 1.5/1.5 | 1.5 | 1.5/1.1 | 3/2.2 | 2.2 |
AC-23 3P/1P (KW) | 2.5/1 | 3.5/2 | 4.5 | 3.7/2.5 | 7.5/3.7 | 7.5 | 5.5/3 | 11/5.5 | 11 |
AC-15(A) | 3 | 2 | - | 5 | 4 | - | 8 | 5 | |
DC-13(A) | 1 | ||||||||
Mechanical Life | 60X104ops,operation frequency:120ops/hour | ||||||||
Electrical Life AC-15 | 20X104ops,operation frequency:300ops/hour | ||||||||
Electrical Life at DC-13 | 6X104ops,operation frequency:300ops/hour |
Model | FW26-32 | FW26-63 | FW26-125 | FW26-160 | ||||||
Rated Insulation Voltage Ui (V) | 690V | |||||||||
Rated Thermal Current Lth(A) | 32 | 63 | 125 | 160 | ||||||
Rated Operating Voltage Ue (V) | 220 | 380 | 500 | 220 | 380 | 500 | 220 | 380 | 220 | 380 |
AC-21A AC-22A(A) | 32 | 63 | 125 | 160 | ||||||
AC-2 3P(KW) | 7.5 | 15 | 18.5 | 18.5 | 30 | 40 | 30 | 45 | 37 | 55 |
AC-3 3P/1P(KW) | 5.5/4 | 11/5.5 | 11 | 11/6 | 18.5/11 | 18.5 | 15/7.5 | 30/13 | 22/11 | 37/18.5 |
AC-4 3P/1P(KW) | 2.5/1.5 | 5.5/3 | 5.5 | 5.5/2.4 | 7.5/4 | 7.5 | 6/3 | 11/5.5 | 10/4 | 15/7.5 |
AC-23 3P/1P(KW) | 7.5/4 | 15/7.5 | 15 | 15/10 | 30/18.5 | 45 | 30/15 | 45/22 | 37/22 | 75/37 |
AC-15(A) | 14 | 6 | - | |||||||
DC-13(A) | 1.5 | 11 | ||||||||
Mechanical Life | 60X104 ops,operation frequency:120ops/hour | |||||||||
Electrical Life AC-15 | 20X104 ops,operation frequency:300ops/hour | |||||||||
Electrical Life at DC-13 | 6X104 ops,operation frequency 300ops/hour |
◆Dimensions
Outline and mounting size of small panel type
Outline and mounting size of large panel type