◆Product Features
Good safety
●With double-row composite contact,levelly-pulling opening and closing mechanism,micro motor energy pre-stored technology as well as microelectronic control technology,it can basically realize no flashover (no arc chute)
●Adopt reliable mechanical and electrical interlocking
●Due to zero crossing technology,it can set to zero compulsorily under emergency (Cut off double circuit power synchronously)
●With visible indication of on/off position and padlocking function,it can get the space between power supply and load.
High reliability,service life reaching 8000 times
●Being designed with electromechanical integration,the switch transfers accurately,flexibly and smoothly. Superior electromagnetism compatibility,strong capability to resist the interference,no interference to outside
High automation
●The switch has multi-circuit input/output interface that can realize PLC remote control as well as automation of system.
●The switch needn't any external control elements.
Nice appearance,small volume,light weight
●The product conforms to following standards:GB/T 14048.11-2008/1EC60947-6-1 Automatic Transfer Switching Equipment,GB/T14048.3-2008/1EC60947-1 Low-voltage Switchgear and Controlgear General Rules as well as GB/14048.3-2008/IEC60947-3 Low-voltage Switchgear and Controlgear--Low-voltage Switches,Disconnectors,Switch-disconnectors and Fuse-combination units.
Type | Controller | Pole | Electric Grade | Available |
ATS01-32~100 | A,B,D | 3P,4P | PC | INT Series |
ATS01-100 | A,B,D | 3P,4P | NSX-NA | |
ATS01-160 | AB,D | 3P,4P | NSX-NA | |
ATS01-250 | A,B,D | 3P,4P | NSX-NA | |
ATS01-400 | B,D | 3P,4P | NSX-NA | |
ATS01-630 | B,D | 3P,4P | NSX-NA |
◆Main technical indexes
Conventional heating current | 20A | 40A | 60A | 80A | 100A |
Rated insulation voltage Ui | 690V | ||||
Rated impaction withstand voltage Uimp | 8KV | ||||
Rated working voltage Ue | AC380V | ||||
Rated working current le | 20A | 63A | 63A | 80A | 100A |
Load character | AC33iB | ||||
Rated making capacity | 10le | ||||
Rated breaking capacity | 8le | ||||
Rated limiting short-circuit current | 50KA | ||||
Rated short time withstand current le | 7KA | ||||
Change-over time | 1S | ||||
Voltage of control power supply | AC220V | ||||
Energy consumption of the motor | 40W | ||||
Weight Kg | 4.2 | 4.3 | 4.4 | 4.5 | 4.5 |
◆Main technical indexes
Conventional heating current | 125A | 160A | 250A | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | 2500A | 3200A | |
Rated insulation voltage Ui | 800V | ||||||||||||
Rated impaction withstand voltage Uimp | 8KV | 12KV | |||||||||||
Rated working voltage Ue | AC440V | ||||||||||||
Rated working current le | AC-32B | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1000 | 1250 | 2000 | 2000 | 2500 |
Rated making capacity | 17KA | 25.2KA | 34KA | ||||||||||
Rated breaking capacity | 20KA | 50KA | |||||||||||
Rated limiting short-circuit current | 10KA | 12.6KA | 20KA | ||||||||||
Rated short time withstand current IS | 2S | 3S | |||||||||||
Change-over time | AC220V | ||||||||||||
Voltage of control power supply | |||||||||||||
Energy consumption of the | Start | 300W | 325W | 355W | 400W | 440W | 600W | ||||||
Normal | 55W | 62W | 74W | 90W | 98W | 120W | |||||||
Weight Kg | 4-pole | 7.5 | 8.8 | 9 | 16.5 | 17 | 32 | 36 | 40 | 49 | 95 | 98 | 135 |